What are tested electrical panels?

Writer: BTM
BTM
Sep 25, 2025
3 min read

Have you ever wondered why two seemingly identical electrical panels can behave completely differently in the field? The answer lies in testing. A panel may perfectly meet specifications on paper, but fail catastrophically under the first real overload if it hasn't been properly tested.


The difference between a panel that "works" and a reliable panel lies precisely in the validation through standardized tests. It is the distinction between a technical promise and a proven guarantee of performance.



What does "test panel" really mean?


A tested electrical panel is not just a piece of equipment that has undergone some basic tests. It is a system that has been subjected to a rigorous battery of checks that simulate the most severe conditions it may face during its period of operation.


The tests validate everything from the ability to withstand short-circuit currents to continuous temperature rise. They verify whether the seals actually protect against dust and water, whether the insulating materials maintain their properties under thermal stress, and whether the protection mechanisms act at the correct times.


This validation is especially critical in medium-voltage switchgear, where faults can cause electrical arcs with enough energy to vaporize metal and cause explosions. The difference between a tested and an untested switchgear can literally be a matter of life or death.



Type testing: validating the entire design.


Type tests are performed only once for each panel design, but their implications extend to the entire product family based on that design. It's like a "proof of concept" that proves the engineering behind the panel is sound.


The temperature rise test is one of the most critical. The panel is energized with nominal current for several hours while thermocouples monitor temperatures at specific points. Busbars cannot exceed temperatures above the recommended level, while cable terminals are limited to 70°C. These limits ensure that insulating materials do not degrade prematurely.


The short-circuit resistance test places the panel under extreme conditions. Currents up to 100 times the nominal current are applied for defined periods, simulating severe faults. The panel must maintain structural integrity, contain electrical arcs, and allow normal operation after the test.


Checking the IP protection rating confirms whether the seals actually work. Pressurized water jets or dust chambers test the effectiveness of the seals under controlled conditions. An IP54 panel should prevent the ingress of harmful dust and withstand water splashes from any direction.



Routine testing: individual guarantee of each panel.


While type tests validate the design, routine tests verify that each individual panel was manufactured correctly. These are less stringent tests, but fundamental for detecting manufacturing defects before delivery.


The applied voltage test verifies the integrity of the insulation between energized circuits and grounded metal parts. Voltages higher than the nominal voltage are applied for specific periods to ensure that the insulation can withstand operational overvoltages.


Verifying the continuity of the protective circuit confirms that all metallic parts are properly connected to the grounding system. Resistances above specified values can cause dangerous voltages during faults.


Functional tests verify that protection and switching devices operate correctly. Relays are tested at their set points, circuit breakers are activated to check opening and closing times, and interlocking systems are validated.



Technical standards: the safety framework


ABNT NBR IEC 61439 establishes requirements for low-voltage switchgear, defining detailed criteria for each type of test. The standard specifies not only what to test, but how to test it, including equipment configurations, durations, and approval criteria.


For medium-voltage switchgear, ABNT NBR IEC 62271 defines even more stringent requirements. The energies involved are higher, making faults potentially more destructive. The standard establishes arc resistance classes, which determine the time the switchgear must contain arcs without allowing the ejection of energized parts.


NR-10 complements these technical standards with occupational safety requirements. It establishes that equipment installed in workplaces must have documentation certifying compliance with Brazilian or international technical standards.



Interpreting test reports


A well-prepared test report documents all tests performed, test conditions, equipment used, and results obtained. It should include photographs of the test setup, temperature versus time graphs, and measurements of all relevant quantities.


Traceability is fundamental. Measuring equipment must have valid calibration certificates, preferably traceable to INMETRO. This ensures that measurements are reliable and repeatable.



The testing process and its importance.


Laboratories accredited by INMETRO follow rigorous quality control procedures and are audited regularly.


The typical process includes analysis of technical documentation, inspection of manufacturing facilities, type testing on representative samples, and periodic production audits.


Regulatory documents are valid for a specific period and must be renewed regularly.







 
 
 